Call:755-29769042 ENGLISH 简体中文

Home>Supports>Technical Supports

Technical Supports

Can REIGN POWER's power supply be used in the range of 45Hz ~ 440Hz? If YES, is there anything special will happen ?

Source:本站Release Date:2024-04-27

REIGN POWER's power supply can be used within this frequency range. But if the frequency is too low, the efficiency will also be lower. For example, when a RP1320-24C is operated under 230VAC and rated load, if the frequency of AC input is 60 Hz, the efficiency is around 84%; however, if the frequency of AC input reduces to 50 Hz, the efficiency will be around 83.8%. Besides, if the frequency is too high, the power factor of the S.P.S. with PFC (power factor correction) function will reduce and this also will cause higher leakage current. For example, when a RP1320-24C is operated under 230VAC and rated load, if the frequency of AC input is 60 Hz, the power factor is 0.95 and the leakage current is around 0.72mA; however, if the frequency of AC input increase to 440 Hz, the power factor will decrease to 0.78 and the leakage current will rise to around 4.2mA.